• Murphy

Model 12 Air Temperature Sensor

The Model 12 Air Temperature Sensor is intended for use in applications that monitor slowly changing temperature. 

The unit gives approximately .5 °F (.25 °C) resolution when used with an 8-bit analog input.

Specifications Downloads How to Order
X
Specifications Drawer: 

Temperature Capability

  • Useful Operating Temperature Range: 0°F to 115°F (-18°C to 46°C)
  • Component Temperature Range: -85°F to 300°F (-65°C to 150°C)
  • Accuracy: 2% of full scale with software offset correction.

Voltage

  • Power Input Voltage: 9 to 28 VDC
  • Current Draw: 1mA
  • Cable: 2 foot length, 22 AWG, stranded
  • Clamp: 1/2” ID, provided (P/N 00-03-0392)

Temperature Sensing Range

VDC Out°C°F
0.00-180
0.25-14.55.8
0.50-11.411.5
0.75-8.217.3
1.00-523.0
1.25-1.828.8
1.501.434.5
1.754.640.3
2.007.846.0
2.251151.8
2.5014.257.5
2.7517.463.3
3.0020.669.0
3.2523.874.8
3.502780.5
3.7530.286.3
4.0033.392.0
4.2536.697.8

WARNING: This product can expose you to chemicals including lead, which are known to the State of California to cause cancer, birth defects or other reproductive harm. For more information about California Propsition 65, go to www.P65Warnings.ca.gov or visit our California Proposition 65 page.

Literature Drawer: 

Additional product documentation can be found on our product support website or by clicking the Help Center button above.

Primary Method - Table: 
Part NumberModel/Description
10707483Model 12: Air Temperature Sensor